Fan Filter Unit (FFU)

Fan Filter Unit (FFU)

  • Category:other
  • Browse number:
  • QR code:
  • Release time:2022-09-13 09:57:27
  • Product description

Product Features:

Built-in fan filter unit


Lower power consumption and lower operating costs


Built-in duct diversion system, reduce noise and pressure loss, improve the efficiency of the fan


Can be customized non-standard specifications, supporting a variety of different keel structure


Suitable for class 100, class 1000 turbulence and laminar flow clean room





Product efficiency:

Efficiency level: H13 (99.9%@0.3μm)

                          H14(99.99%@0.3μm)

                          U15(99.9995%@0.12μm)

                          U16(99.99995%@0.12μm)





Product Application:

Fan filter unit with its own filter unit, suitable for strict control of the cleanliness of the environment, such as semiconductor, pharmaceutical, electronic clean room. It can be upgraded according to different site design requirements to achieve different cleanliness requirements.





Installation method:

Wind direction: the direction indicated by the arrow on the product label





Product material and operating conditions:

boxAluminum plated zinc iron/Aluminum alloy/stainless steel
Electric machineAC/EC
Power sourceAC-220V-50HZ
Control modeComputer group control/manual knob control
assortingRunning indicator light, fault indicator light, pressure difference alarm device, etc






Product selection and naming rules:




AC AC - Performance parameters:

Nominal sizeActual size(mm)

Total pressure

(Pa)

Energy consumptionnoiseweightFace air velocity filter size
WXHW×H@0.45m/sWdBAkgm/sW×H
2×2575×57519070-9050-5515-180.45570×570
4×21175×575280130-15050-5523-270.451170×570
4×41175×1175230220-25552-5837-420.451170×1170
Note: Please contact sales for different operating environments





EC DC performance parameters:

Nominal size(W×H)4×24×4
Actual size(mm)1175×575 1175×1175

Surface wind speed

(m/s)

0.450.45
Filter size(mm) 1170×570×701170×1170×70
Filter materialUltrafine glass fiberUltrafine glass fiber
Air volume(CMH)11002200

External static 

pressure(Pa)

0501000 50100
Filter efficiencyH13U15H13U15H13U15H13U15H13U15H13U15
Total pressure(Pa)9511514516519521595115145165195215
Energy consumption(W)496065809010095110130140 165190
noise(dBA)424546484750454649505152
Note: 1, resistance tolerance is ±10%; 2, special size please contact sales personnel